Product Description
The Fully Insulated SF6 Ring Main Unit is a fully insulated, fully isolated electrical Ring Main Unit developed for cable circuit applications. This RMU uses SF6 gas for insulation, which effectively minimizes the impact of harsh environments. With an excellent reputation, it is used in municipal electrical grids throughout China.

Technical Parameters
|
Item |
Unit |
C Module |
F Module |
V Module |
CB Module |
||
|
Load Switch |
Switch-Fuse Combination |
Vacuum Switch |
Disconnector/ Earthing Switch |
Vacuum Switch |
Disconnector/Earthing Switch |
||
|
Rated Voltage |
KV |
12 |
12 |
12 |
12 |
12 |
12 |
|
Rated Frequency |
HZ |
50 |
50 |
50 |
50 |
50 |
50 |
|
Power Frequency Withstand Voltage(Phase-to-Phase/Across Break) |
KV |
42/48 |
42/48 |
42/48 |
42/48 |
42/48 |
42/48 |
|
Lightning Impulse Withstand Voltage |
KV |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
75/85 |
|
Rated Current |
A |
630 |
630 |
1250/630 |
|||
|
Breaking Capacity: |
|||||||
|
Rated Closed-Loop Breaking Current |
A |
630 |
|||||
|
Rated Cable Charging Breaking Current |
A |
10 |
|||||
|
Rated Short-Circuit Making Current(Peak) |
A |
50 |
80 |
||||
|
Rated Peak Withstand Current |
KA |
50 |
|||||
|
Rated Short-Time Withstand Current |
KA/35 |
20 |
|||||
|
Rated Short-Circuit Breaking Current |
KA |
31.5 |
20 |
25 |
|||
|
Rated Transfer Current |
A |
1700 |
|||||
|
Max.Fuse Rating |
A |
125 |
|||||
|
Loop Resistance |
≦300 |
≦600 |
|||||
|
Mechanical Life |
Times |
5000 |
3000 |
5000 |
2000 |
5000 |
5000 |
Advantages
- Uses mechanical and electrical logical interlocking mechanisms that prevent misoperation.
- Allows all operations to be carried out without opening the door for complete safety.
- Ensures zero potential at the interface with completely grounded system design
- Avoid live operation with isolated compartment design.
- Allows for customization by using modular components as needed.
- Installs simply and conveniently with ample room for cable connection.
Applications
- Urban and rural distribution networks
- Industrial parks and factories
- Wind farms and photovoltaic power stations
- Public infrastructure
Frequently Asked Questions
Q1: What is the maintenance requirement for the Fully Insulated SF6 Ring Main Unit?
A: The switchgear is designed for maintenance-free operation under normal working conditions.The fully sealed SF6 gas insulation system protects internal components from environmental factors such as dust,moisture,and corrosion.However,we recommend an annual visual inspection and a comprehensive check every 5-8 years by qualified personnel to ensure optimal performance.
Q2: Is SF6 gas environmentally friendly?
A: SF6 is an excellent insulating medium with superior arc-quenching properties.While it has a high global warming potential,our switchgear is designed with a fully sealed stainless steel enclosure to prevent gas leakage.The gas can be recycled and reused at the end of the equipment's lifecycle,minimizing environmental impact.We also comply with all relevant regulations for SF6 handling and recycling.
Q3: Can the switchgear be expanded in the future?
A: Yes.Our Fully Insulated SF6 Ring Main Unit features a modular design with expandable busbars.Additional units can be connected on-site to accommodate load growth or system modifications without replacing the entire switchgear assembly,providing excellent long-term flexibility.
Hot Tags: fully insulated sf6 ring main unit, China fully insulated sf6 ring main unit manufacturers, factory, outdoor prefabricated enclosed ring main unit, Fully Insulated SF6 Ring Main Unit, Non Metal Enclosed RMC Box, Solid Insulated Ring Main Unit, Dry Air Insulated Ring Main Unit, Metal Enclosed RMC Box