38kV Meta-Clad Switchgear

38kV Meta-Clad Switchgear

Details
38kV Meta-Clad Switchgearr comes with vacuum circuit breakers, and it can be custom engineered for a range of indoor and outdoor setups. You’ve got a few flexible configuration options to pick from, including single aisle layouts, common aisle layouts, or full integration into a Power Control Center.
Category
Medium Voltage Switchgear
Share to
Send Inquiry
Description
Technical Parameters

Product Description

 

38kV Meta-Clad Switchgearr comes with vacuum circuit breakers, and it can be custom engineered for a range of indoor and outdoor setups. You've got a few flexible configuration options to pick from, including single aisle layouts, common aisle layouts, or full integration into a Power Control Center. This kind of control center usually holds transformers, low voltage AC or DC switchgear,and all the necessary support systems right alongside it.

product-700-700

 

Circuit Breaker Technical Parameters

 

Item

Unit

Parameter

ZN85A-40 3AH3

SF1/SF2

Rated Voltage

 

kV

40.5

Rated Insulation Level

Lightning Impulse Withstand Voltage(Full Wave)

kV

185

Power Frequency Withstand Voltage(1 min)

95

Rated Frequency

Hz

50

Rated Current

A

1250;1600;2000

630;1250;2500

Rated Short-Circuit Breaking Current

kV

20,25,31.5

25,31.5

Rated Short-Circuit Making Current(Peak)

kV

50,63,80

63,80

Rated Dynamic Current(Peak)

kV

50,63,80

63,80

4s Thermal Current(RMS)

kV

20,25,31.5

25,31.5(3s)

Opening Time

ms

36-60

≤ 45

Closing Time

ms

40-90

≤ 75

Rated Operating Sequence

 

O-0.3s-CO-180s-CO

 

Advantages

 

Uses those advanced vacuum circuit breakers.

Compartmentalized construction,so each device gets its own breaker compartment,nice and separated.

Load and incoming connections are at the back,which makes for easy access.

Works for indoor or outdoor applications,and you can choose between non walk-in or walk-in enclosures depending on what you need.

 

Applications

 

Utility Substations

Oil and Gas Facilities

Heavy Industrial Plants

Power Generation

Infrastructure Projects

 

Frequently Asked Questions

 

Q1: What are the applicable environmental conditions for this switchgear?

A: This product is designed to handle a pretty standard range of conditions.Ambient temperature wise,it will run fine anywhere from minus 10 to plus 40 degrees Celsius.Altitude shouldn't go above 1000 meters above sea level.For humidity,the daily average needs to stay under 95 percent,and the monthly average under 90 percent.You also want to avoid placing it where there's corrosive gases,heavy pollution,flammable gases,or a lot of intense vibration.On the seismic side,it can safely handle areas where the earthquake intensity doesn't exceed magnitude 8 on the MSK scale.

Q2: What defines "metal-clad" construction at 38kV?

A: So according to IEEE C37.20.2,for something to be called metal clad,it needs to have draw-out circuit breakers,grounded metal barriers between the major compartments,and all the live parts have to be fully enclosed in grounded metal.Our 38kV Meta-Clad Switchgear checks all those boxes,with individually grounded steel compartments for the breakers,the bus,and the cables.

Q3: What are the standard ratings available?

A: For standard ratings,you're looking at continuous current from 1200 amps up to 3000 amps,short-circuit interrupting ratings going as high as 40kA symmetrical,and a basic impulse level,or BIL,of 150 kilovolts peak.And if you need to push the continuous current even further,forced cooling options are available to extend that capability.

 

Hot Tags: 38kv meta-clad switchgear, China 38kv meta-clad switchgear manufacturers, factory, XGN2 12 Switchgear, KYN61 40 5 Switchgear, Medium Voltage Air Insulated Switchgear, 35kV Switchgear, 20kV Switchgear, Flameproof Switchgear

Send Inquiry
Contact us if have any question

You can either contact us via phone, email or online form below. Our specialist will contact you back shortly.

Contact now!